Example loops / Level

Level control and high trip

V-1101 LT 1101 LIC 1101 LV-1101 LSHH 1101 TRIP Closes inlet on high high

Tag list

  • LT-1101 Level transmitter on V-1101
  • LIC-1101 Level indicating controller (DCS)
  • LV-1101 Level control valve on outlet
  • LSHH-1101 High high level switch (separate from BPCS)

How it works

LIC-1101 modulates LV-1101 to hold drum level. LSHH-1101 is a separate switch. On high high level it trips inlet feed closed. Planners treat the trip device as safety related scope, not as a spare controller faceplate.

Esc to close · powered by a static index